  "title": "CARZ explosion-isolation flap valve selection guide",
  "kind": "reference",
  "company": "Nederman",
  "category": "Cleaning, recycling & protection",
  "parameters": {
    "Function": "Passive explosion isolation",
    "Valve families": "CARZ; CARZ-N; B-Flap",
    "Certified test standard": "EN 16447:2014",
    "European directive": "ATEX 2014/34/EU",
    "NFPA reference": "NFPA 69",
    "Additional certification": "IECEx for CARZ-N"
  },
  "summary": "CARZ and B-Flap valves are passive isolation devices installed in dust-collection ducting to reduce upstream propagation of the pressure wave and flame generated by a collector explosion. Selection depends on system pressure mode, installation location, duct and process conditions, and the applicable protection standard.",
  "sections": [
    {
      "heading": "Isolation function",
      "paragraphs": [
        "An explosion inside a dust collector can propagate through connected ducting toward the work area. A correctly selected and installed isolation flap is intended to close under the event pressure wave, limiting reverse propagation into machinery and occupied areas.",
        "Isolation is one layer of a combustible-dust protection strategy. It does not replace prevention, collector venting or suppression, grounding, housekeeping, and control of ignition sources where those measures are required."
      ]
    },
    {
      "heading": "Verified compliance references",
      "rows": [
        [
          "Valve families",
          "CARZ, CARZ-N and B-Flap"
        ],
        [
          "Test and certification basis",
          "EN 16447:2014"
        ],
        [
          "European equipment directive",
          "ATEX 2014/34/EU"
        ],
        [
          "North American design reference",
          "NFPA 69 compliance is stated"
        ],
        [
          "Additional certification",
          "CARZ-N variants are stated as IECEx certified"
        ],
        [
          "Purpose",
          "Isolation between the collector and upstream process or work area"
        ]
      ]
    },
    {
      "heading": "Selection inputs",
      "paragraphs": [
        "Start with dust explosibility data and the complete protection concept. Identify whether the conveying system is high or low vacuum, negative-pressure pull or positive-pressure push, and whether the valve is installed indoors or outdoors.",
        "Confirm duct size and orientation, normal operating pressure and airflow, expected reduced explosion pressure, allowable installation distance and the certified operating envelope of the exact valve variant. Some combinations have limitations and must be checked against current technical data."
      ]
    },
    {
      "heading": "Inspection and lifecycle control",
      "paragraphs": [
        "Keep the flap and locking mechanism free of buildup, corrosion and mechanical damage. Inspection access must not compromise duct integrity, and the valve must be returned to its specified operating position after service.",
        "After any suspected explosion or abnormal pressure event, isolate the system and have the valve and connected protection equipment inspected before restart. Changes to dust, ducting, fan direction or process pressure require the isolation design to be reassessed."
      ]
    }
  ],
  "updated_at": "2026-10-14T08:28:54.994Z"
}