CARZ explosion-isolation flap valve selection guide

CARZ and B-Flap valves are passive isolation devices installed in dust-collection ducting to reduce upstream propagation of the pressure wave and flame generated by a collector explosion. Selection depends on system pressure mode, installation location, duct and process conditions, and the applicable protection standard.

Product & technical referenceNedermanCleaning, recycling & protection

Technical profile

Manufacturer / publisherNederman
FunctionPassive explosion isolation
Valve familiesCARZ; CARZ-N; B-Flap
Certified test standardEN 16447:2014
European directiveATEX 2014/34/EU
NFPA referenceNFPA 69
Additional certificationIECEx for CARZ-N
CategoryCleaning, recycling & protection
Updated2026-10-14T08:28:54.994Z

Isolation function

An explosion inside a dust collector can propagate through connected ducting toward the work area. A correctly selected and installed isolation flap is intended to close under the event pressure wave, limiting reverse propagation into machinery and occupied areas.

Isolation is one layer of a combustible-dust protection strategy. It does not replace prevention, collector venting or suppression, grounding, housekeeping, and control of ignition sources where those measures are required.

Verified compliance references

Valve familiesCARZ, CARZ-N and B-Flap
Test and certification basisEN 16447:2014
European equipment directiveATEX 2014/34/EU
North American design referenceNFPA 69 compliance is stated
Additional certificationCARZ-N variants are stated as IECEx certified
PurposeIsolation between the collector and upstream process or work area

Selection inputs

Start with dust explosibility data and the complete protection concept. Identify whether the conveying system is high or low vacuum, negative-pressure pull or positive-pressure push, and whether the valve is installed indoors or outdoors.

Confirm duct size and orientation, normal operating pressure and airflow, expected reduced explosion pressure, allowable installation distance and the certified operating envelope of the exact valve variant. Some combinations have limitations and must be checked against current technical data.

Inspection and lifecycle control

Keep the flap and locking mechanism free of buildup, corrosion and mechanical damage. Inspection access must not compromise duct integrity, and the valve must be returned to its specified operating position after service.

After any suspected explosion or abnormal pressure event, isolate the system and have the valve and connected protection equipment inspected before restart. Changes to dust, ducting, fan direction or process pressure require the isolation design to be reassessed.